Energy Saving Case Study –
Portaflow 300 measurements facilitate major savings

Micronics Portaflow 300 portable flow meter used to measure actual flow rates on an existing 75kW
motor pump circuit in a process application, which led to the replacement of the pump with a smaller
11kW unit and major savings!
Energy Saved
Annual Energy Consumption reduced from £5698.00 to £926.00!
Capital Cost £1500.00 and payback in 4 months! |
Potential for Replication – 1000’s in Industrial Process and Building Services applications where pumps
are frequently oversized and cost effective non-invasive monitoring can identify the potential for significant
savings without the costs and disruption associated with drain downs, process disruption and down time!
Company
Micronics Ltd is a UK based company established for 20 year
with customers in over 40 countries. They can help solve most
flow and energy metering and monitoring requirements with
their range of non-invasive “Ultrasonic Clamp on” flow and energy
meters, offering significantly lower cost installation and operating
costs than alternative in-line meters.
Application Details
Installed pump: Ingersoll Rand 150-125-250 end suction pump,
75kW 2900-rpm motor.
The installed pump was supplied from a high level suction tank (CLT1) and delivered process water through
a two stage condenser back to a balance tank (CLT2). It was observed that a flow control valve, installed in the discharge pipework, was only 20% open! Process flow requirements were relatively constant.
INVESTIGATION PROCEDURE
1) The flow required to the condenser was recorded using a Micronics Portaflow 300 non-invasive flow
meter.
2) Pressure gauges were fitted:
a) at the pump to determine actual generated pressure head.
b) before and after the condenser to determine actual pressure requirement.
3) Power input was recorded using a kW power analyser.
| |
|
The Micronics PF300 - an indispensable tool
|
|
 |
CONCLUSION
After obtaining the manufacturers data curve and analysis of the existing pump
recorded performance, it was concluded that:
1) The pump was too large for the flow rate required, this was resulting in poor efficiency as the operating
point was back-up' the curve in an inefficient area.
2) 33m head was being wasted across the control valve = 66% wasted energy!
3) The pump was providing a 50m head but the total head requirement was only 17m!
4) The pump should be changed to an appropriate size for the circuit load.
Micronics Portaflow 300
The Portaflow 300 measures the flow of liquid within a pipeline through two sound transmitter/receivers
clamped to the outside of the pipe wall. The sound is directed through the pipe wall into the flowing liquid where the speed of the sound wave is modulated by the flowing liquid. This modulation is converted into volume flow rate by the electronics in the flow meter. There are no mechanical moving parts required either